Technical Specifications 

Rating 850VA/600W
Format Tower or 1RU Rack

Electrical characteristics 

Technology Line-Interactive High Frequency (Pure Sinewave, Booster + Fader)
Input voltage and frequency rages
without using batteries
16V-294V (adjustable to 150V-294V) 47 to 70 Hz (50 Hz system),
56.5 to 70 Hz (60 Hz system), 40 Hz in low-sensitivity mode
Output voltage and frequency

230 V (+6/-10%) (Adjustable to 200V / 208V / 220V / 230V / 240V)
50/60 HZ +/-0.1% (autosensing)

Connections 

Input Tower: Fixed line cord 10A AU 1.8mtr
Rack: IEC C14 (10A) socket
Output Tower: 2 x AU 10A,3 x IEC C13 (10A)
Rack: 4 x IEC C13 (10A)
Remotely controlled sockets Tower: 2 x10A AU individually switched
Rack: 2 x IEC C13 (10A0), individually switched

Batteries Typical backup times for 50 and 70% load*

5P 9/5.5 mins
Battery management ABM® & Temperature compensated charging method (user selectable), Automatic battery test,
deep discharge protection, to automatic recognition of external battery units

Interfaces 

Communications ports 1 USB port + 1RS2323 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously)
+ 1 mini terminal block for remote ON/OFF or Remote Power Off
Communications card slots

1 slot for NETWORK-MS, MODBUS-MS or RELAY-MS cards

Operating Conditions, standards and approvals

Operating temperature Models 650, 850 & 1550 = "0-35°C", Model 1550 = "0-40°C"
Noise Level <40dBA
Performance - Safety - EMC IEC/EN 62040-1-1 (Safety), IEC/EN 62040-2 (EMC), UEC/EN 62040-3 (Performance), C-Tick
Approvals CE, CB report, TUV

Dimensions W x D x H / Weight 

UPS Dimensions (mm) & weight (kg) - Tower 150 x 345 x 230mm / 10.4kg
UPS Dimensions (mm) & weight (kg) - Rack 438 x 509 x 43.2mm(1RU) / 13.8kg

Customer Service & Support 

Warranty 3 years on electronics, 2 years on batteries

Part Numbers

5P Tower 5P850AU
5P Rack 5P850iR