Technical Specifications |
|
Rating | 2200 VA / 1980 W |
Format | RT2U (tower / rack 2U) |
Electrical characteristics |
|
Technology | Line-Interactive High Frequency (Pure Sinewave, Booster + Fader) |
Input voltage and frequency ranges | 160V-294V (adjustable to 150V-294V) 47 to 70 Hz (50 Hz system), |
without using batteries | 56.5 to 70 Hz (60 Hz system), 40 Hz in low-sensitivity mode |
Output voltage and frequency | 230 V (+6/-10 %) (Adjustable to 200V / 208V / 220V / 230V / 240V), 50/60 Hz +/- 0.1 % (autosensing) |
Connections |
|
Input | 1 IEC C20 (16 A) socket |
Outputs | 8 IEC C13 (10 A) sockets, 1 IEC C19 (16 A) socket |
Remotely controlled sockets | 2 groups of 2 x IEC C13 (10 A) |
Additional outputs with Hot Swap MBP | 4 AUS 10A + 1 IEC 16A sockets or 6 IEC 10 A sockets or terminal blocks (HW version) |
Additional outputs with FlexPDU | 6 AUS 10A + 1 IEC 16A sockets or 12 IEC 10 A sockets |
Batteries Typical backup times for 50 and 70% load* |
|
5PX | 15/8 mins |
5PX + 1 EBM | 60/35 mins |
5PX + 4 EBM | 210/125 mins |
Battery management | ABM® & Temperature compensated charging method (user selectable), Automatic battery test, deep discharge protection, automatic recognition of external battery units |
Interfaces |
|
Communication ports | 1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously) + 1 mini terminal block for remote ON/OFF and Remote Power Off |
Communications card slots | 1 slot for NMC Minislot card or NMC ModBus/JBus or MC Contacts/Serial |
Operating conditions, standards and approvals |
|
Operating temperature | 0 to 40°C |
Noise Level | < 45 dBA |
Performance - Safety - EMC | IEC/EN 62040-1-1 (Safety), IEC/EN 62040-2 (EMC), IEC/EN 62040-3 (Performance), C-Tick |
Approvals | CE, CB report, TÜV |
Dimensions W x D x H / Weight |
|
UPS Dimensions (mm) | 441 x 522 x 86.2 (2U)mm |
UPS Weight (kg) | 28.5kg |
Dimensions of EBM | same as UPS |
Weight of the EBM | 32.8kg |
Customer Service & Support |
|
Warranty | 3 years on electronics, 2 years on batteries |
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.