INPUT | 
||
| Voltage Range | Low Line Transfer | 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5% (based on load percentage 100% - 80% / 80% - 70% / 70% - 60% / 60% - 0%)  | 
| Low Line Comeback | 175 VAC ± 5% | |
| High Line Transfer | 300 VAC ± 5% | |
| High Line Comeback | 47.5Hz ~ 52.5Hz or 57Hz ~ 63Hz | |
| Frequency Range | 47.5Hz ~ 52.5Hz or 57Hz ~ 63Hz | |
| Phase | Single phase with ground | |
| Power Factor | 0.98 | |
OUTPUT | 
||
| AC Voltage Regulation (Batt. Mode) | ± 3% | |
| Frequency Range (Synchronized Range | 48Hz ~ 52Hz or 57Hz ~ 63Hz | |
| Frequency Range (Batt. Mode) | 50Hz ± 0.25Hz or 60Hz ± 0.3Hz | |
| Load Crest Factor | 3:1 | |
| Harmonice Distortion | 3% THD (Linear Load) 6% THD (Non-linear Load) | |
| Transfer | AC Mode to Batt. Mode | Zero | 
| Inverter to Bypass | 4ms (Typical) | |
| Waveform (Batt. Mode) | Pure Sinewave | |
EFFICIENCY | 
||
| ECO Mode | 85% | |
| Battery Mode | 83% | |
BATTERY | 
||
| Battery Type | 12Vx9AH(x3) | |
| Typical Recharge Time | 4 Hours to Recover to 90% Capacity | |
| Charging Time (Max.) | 1.0A | |
| Charging Voltage | 41.0 VDC ± 1% | |
PROTECTION | 
||
| Full Protection | Overload, discharge, thermal, short circuit and overcharge protection | |
COMMUNICATIONS & MANAGEMENT | 
||
| Interface | USB or RS232 as standard, Intelligent slot for PSSNMP  or PSA400 dry contact  | 
|
| Software | 
 Power Shield NetGuard Software - supports Windows based operating Systems, Linux, Unix & Mac  | 
|
| LCD Display / Alarm | UPS Status, Load Level, Battery Level, Input/Output Voltage, Battery Time Remaining and Fault Indicators  | 
|
| Audible Alarm | Battery Mode, Low Battery, Overload, Fault | |
PHYSICAL | 
||
| Dimenesion (D x W x H) | 396 x 145 x 240mm | |
| Weight | 14kg | |
OPERATING ENVIRONMENT | 
||
| Temperature | 0°C - 40°C | |
| Humidity | 20-90% (RH Non-condensing) | |
| Noise Level | Less than 45dBA @ 1 Meter | |
COMPLIANCE | 
||
| Safety | EN62040-1-1 2003, IEC60950-1-1 | |
| EMS | EN62040-2 2006 | |
| RoHS | Directive 2001 / 65 / EU | |