INPUT
|
| Voltage Range |
Low Line Transfer |
160Vac / 140Vac / 120Vac / 110Vac ± 5% (based on load percentage 100% - 80% / 80% - 70% / 70% - 60% / 60% - 0) |
| Low Line Comeback |
170Vac / 150Vac / 130Vac / 120Vac ± 5% |
| High Line Transfer |
300Vac ± 5% |
| High Line Comeback |
290Vac ± 5% |
| Frequency Range |
40Hz - 70Hz |
| Phase |
Single phase with ground |
| Power Factor Correction |
>0.99 @ nominal voltage (100% load) |
OUTPUT
|
Output Power Factor: 0.9 |
| Output Voltage (AC Mode) |
240Vac (Selectable 208/220/230/240Vac) |
| Voltage Regulation (Batt. Mode) |
±1% |
| Frequency Range (Batt. Mode) |
50Hz or 60Hz ±1Hz |
| Current Crest Ratio |
5:1 (max.) |
| Transfer Time |
4ms (Typical) |
EFFICIENCY
|
| ECO Mode (Advanced) |
98% |
| Battery Mode |
87% |
| BATTERY |
| Battery Type & Number |
12 V*9AH (x6) |
| Typical Recharge Time |
4 hours recover to 90% capacity. |
| Charging Current (max.) |
Standard Model -1.5Amp, Long Run Model - 1Amp/2Amp /4Amp/6Amp (factory default is 6Amp) |
PROTECTION
|
| Full Protection |
Overload, discharge, thermal, short circuit and overcharge protection |
| Surge Protection |
984 Joules / 22000 Amps |
COMMUNICATIONS & MANAGEMENT
|
| Interface |
USB or RS232 as standard, Intelligent slot for PSSNMP, PSModbus or PSAS400 dry contact |
| Software |
PowerShield NetGuard® software - supports Windows-based operating systems, Linux, Unix and Mac |
| LCD Display / Alarm |
UPS Status, Load & Battery Level, Input/Output Voltage, Batt. Time Remaining and Fault Indicators |
| Audible Alarm |
Battery Mode, Bypass Mode, Low Battery (Batt. Mode), Fault, Overload |
PHYSICAL
|
| Dimension (D x W x H) |
600 x 438 x 88 mm |
| Weight |
29.6kg |
OPERATING ENVIRONMENT
|
| Tempertature |
0 - 40°C |
| Humidity |
20 - 90% (RH Non-Condensing) |
| Noise Level |
< 50dBA @ 1 Meter |
COMPLIANCE
|
| Safety |
EN62040-1-1 2003, IEC60950-1-1 |
| EMC |
EN62040-2 2006 |
| RoHS |
Directive 2011/65/EU |