Technical Specifications

Rating 1500 VA / 1350 W
Format RT2U (tower / rack2U)

Electrical characteristics

Technology Line-Interactive High Frequency (Pure Sinewave, Booster + Fader)
Input voltage and frequency ranges 160V-294V (adjustable to 150V-294V) 47 to 70Hz (50Hz system),
without using batteries 56.5 to 70 Hz (60Hz system), 40Hz in low-sensitivity mode
Output voltage and frequency 230 V (+6/-10 %) (Adjustable to 200V / 208V / 220V / 230V / 240V), 50/60 Hz +/- 0.1 % (autosensing)

Connections

Input 1 IEC C14 (10 A) socket
Outputs 8 IEC C13 (10 A)
Remotely controlled sockets 2 groups of 2 x IEC C13 (10 A)
Additional outputs with Hot Swap MBP 4 AUS 10A + 1 IEC 16A sockets or 6 IEC 10 A sockets or terminal blocks (HW version)
Additional outputs with FlexPDU 6 AUS 10A + 1 IEC 16A sockets or 12 IEC 10 A sockets

Batteries Typical backup times for 50 and 70% load* 

5PX 19/11 mins
5PX + 1 EBM 90/54 mins
5PX + 4 EBM 285/180 mins
Battery management ABM® & Temperature compensated charging method (user selectable), Automatic battery test, deep discharge protection, automatic recognition of
external battery units

Interfaces

Communication ports 1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously)
+ 1 mini terminal block for remote ON/OFF and Remote Power Off
Communications card slots 1 slot for NMC Minislot card or NMC ModBus/JBus or MC Contacts/Serial

Operating conditions, standards and approvals

Operating temperature 0 to 40°C
Noise Level < 45 dBA
Performance - Safety - EMC IEC/EN 62040-1-1 (Safety), IEC/EN 62040-2 (EMC), IEC/EN 62040-3 (Performance), C-Tick
Approvals CE, CB report, TÜV

Dimensions W x D x H / Weight

UPS Dimensions (mm) 441x522x86.2 (2U)mm
UPS Weight (kg) 27.6kg
Dimensions of EBM same as UPS
Weight of the EBM 32.8 kg

Customer Service & Support

Warranty 3 years on electronics, 2 years on batteries

* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.