Rating (VA/W) 2200VA/2200W
Format RT3U
Electrical Characteristics
Technology On-line double conversion with Power Factor Correction (PFC) system
Nominal voltage 200/208/220/230/240V
Input voltage range 176-276V without derating (up to 100-276V with derating)
Input frequency range 40-70Hz, 50/60Hz auto selection, frequency converter mode
Efficiency up to 94% in online mode (up to 98% in Hi-efficiency mode)
Connections
Input 1 IEC C20 (16A) or terminal block on HotSwap MBP HW (Hard-Wired)
Outputs 8 IEC C13 (10A) sockets + 2 IEC C19 (16A) sockets
Outputs on HotSwap models 4 FR/Schuko sockets or 3 BS sockets or 6 IEC 10A sockets or terminal blocks (HW version)
Switched outlet group 2 outlet groups
Communication
Communication ports 1 USB port + 1 serial RS232 port + 1 mini-terminal block for remote ON/OFF + 1 mini-terminal block for remote power off + 1 mini-terminal block for output relay
Communications slots 1 slot for Network-MS card (included in netpack versions), ModBus-MS or Relay-MS cards
Operating conditions, standards and approvals
Operating temperature 0 to 40°C
Noise Level 40dB
Safety IEC/EN 62040-1, UL 1778, CSA 22.2
EMC IEC/EN 62040 -2, FCC Class B, CISPR22 Class B
Approvals & markings CE /CB report (TUV) / cULus / EAC /RCM / KC / Energy Star
Dimensions W x D x H / Weight
UPS Dimensions (mm) 130x440x485
UPS Weight (kg) 24.5
Customer Service & Support
Warranty 3 years on electronics, 2 years on batteries