Capacity 3000VA/2700W
Topology True online double- conversion,Pure Sine Wave
INPUT
Voltage Range Low Line Transfer 160Vac / 140Vac / 120 / 110Vac ± 5 % (based on load percentage 100%-80% / 80%-70% / 70%-60% / 60%-0)
Low Line Comeback 175Vac / 155Vac / 135Vac / 125Vac ± 5 %
High Line Transfer 300Vac ± 5 %
High Line Comeback 290Vac ± 5 %
Frequency Range 40Hz - 70Hz
Phase Single phase with ground
Power Factor Correction >0.99 @ nominal voltage (100% load)
OUTPUT
Output Power Factor 0.9
Output Voltage (AC Mode) 240Vac (Selectable 200/208/220/230/240Vac)
Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Batt. Mode) 50Hz or 60Hz ±1Hz
Current Crest Ratio 3:1 (max.)
Transfer AC Mode to Batt. Mode Zero
Inverter to Bypass 4ms (Typical)
Waveform (Batt. Mode) Pure Sine Wave
EFFICIENCY
ECO Mode (Advanced) 97%
Battery Mode 87%
 BATTERY  
 Battery Number (12 V*9AH)   x 6
 Typical Recharge Time   4 hours recover to 90% capacity (for standard model only)
 Charging Current (max.)   Standard Models - 1.5Amp. Long Run Models - 1Amp / 2Amp / 4Amp / 6Amp selectable (factory default is 6Amp)
 PROTECTION  
 Full Protection  Overload, discharge, thermal, short circuit and overcharge protection
 Surge Protection   984 Joules / 22000 Amps
 COMMUNICATIONS AND MANAGMENT  
 Interface  USB or RS232 as standard, Intelligent slot for PSSNMP, PSModbus or PSAS400 dry contact
 Software  PowerShield® NetGuard® software - supports Windows, Linux, Unix and Mac based operating systems
 LCD Display/Alarm  UPS Status, Load & Battery Level, Input/Output Voltage, Batt. Time Remaining and Fault Indicators
 Audible Alarm   Battery Mode, Bypass Mode, Low Battery (Batt. Mode), Fault, Overload
 PHYSICAL  
 Dimension, (D x W x H) mm   600 x 438 x 88
 Weight (kg)   26.8 & 11.6
 OPERATING ENVIRONMENT   
 Temperature   0 - 40°C
 Humidity   20 - 90% (RH Non-condensing)
 Noise Level   < 50dBA @ 1 Meter
 COMPLIANCE  
 Safety / EMC / RoHS   EN62040-1-1 2003, IEC60950-1-1 / EN62040-2 2006 / Directive 2011/65/EU