Rating (VA/W)

700VA / 630W

Format

Tower

Electrical characteristics

Technology

ON-LINE double conversion with automatic bypass and Power factor correction system

Nominal voltage

200/208/220/230/240V

Input voltage range

190V~276V without derating
(up to 120V~276V with derating)

Input frequency range

40~70Hz, 50/60Hz auto selection, frequency converter mode

Connections

Input

1 IEC C14 (10A)

Output

4 AU (10A) sockets

Switched outlet group

2 outlet groups

Batteries

Typical backup times*

300W

14

Battery management

ABM® and Temperature-compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units

Communication 

Communication ports

1x USB port + 1x serial RS232 port + 1x mini-terminal block for Remote Power Off + 1x mini-terminal block for Output relay

Communication slot

1x slot for Network-M2, Network-MS, ModBus-MS or Relay-MS cards

Operating conditions, standards and approvals

Operating temperature

0°C~40°C

Typical noise level

40dB

Safety

IEC/EN 62040-1

EMC

IEC/EN 62040-2 (Emissions, Category C1)

Approvals & markings

CE / CB report (TUV) / RCM

Dimensions HxWxD

252x160x357mm

Weight

11.5kg

* Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.