Specification 
Cells Per Unit 6
Voltage Per Unit 12 V
Capacity 25W @15 minute-rate to 1.67V per cell @25℃ (77°F)
Weight Approx. 1.95 kg(4.30 lbs)
Maximum Discharge Current 130A (5 Sec)
Internal Resistance Approx. 19.6 mΩ
Operating Temperature Range Discharge:-15℃~50℃(5°F~122°F)
Charge:-15℃~40℃(5°F~104°F)
Storage:-15℃~40℃(5°F~104°F)
Nominal Operating Temperature Range 25℃±3℃ (77°F±5°F)
Float Charging Voltage 13.5 to 13.8 VDC/unit Average at 25℃ (77°F)
Recommended Maximum Charging Current Limit 2.5A
Equalization and Cycle Service 14.4 to 15.0 VDC/Unit Average at 25℃(77°F)
Self Discharge It should be more than 75% of the capacity before storage after stocked for 6 months at ambient temp. 25℃
Terminal F2-Faston Tab 250
Container Material ABS(UL94-HB) & Flammability resistance of(UL94-V0) can be available upon request.