Technical Specifications | 1500 | 2000 | 3000 |
Rating(VA/W) | 1500VA/1500W | 2000VA/1800W | 3000VA/2400W (3000VA/3000W with EBM) |
Format | RT2U (tower/rack 2U | ||
Electrical characteristics | |||
Technology | On-line double conversion with Power Factor Correction (PFC) System | ||
Nominal voltage | 200/208/220/230/240V | ||
Input voltage range | 176-276V without derating (up to 100-276V with derating) | ||
Input frequency range | 40-70Hz, 50/60Hz autoselection, frequency converter mode | ||
Efficiency | up to 92.5% in online mode | up to 93.5% in online mode | up to 94% in online mode |
(up to 97.5% in Hi-efficiency mode) | (up to 98% in Hi-efficiency mode) | (up to 98% in Hi-efficiency mode) | |
Connections | |||
Input | 1 IEC C14 (10A) | 1 IEC C14 (10A) | 1 IEC C20 (16A) |
Outputs | 8 IEC C13 (10A) sockets | 6 IEC C13 (10A) + 2 ANZ GPO (10A) sockets | 8 IEC C13 (10A) sockets + 2 IEC C19 (16A) sockets |
Switched outlet group | 2 outlet groups |
Connections | |||
Input | 1 IEC C14 (10A) | 1 IEC C14 (10A) | 1 IEC C20 (16A) |
Outputs | 8 IEC C13 (10A) sockets | 6 IEC C13 (10A) + 2 ANZ GPO (10A) sockets | 8 IEC C13 (10A) sockets + 2 IEC C19 (16A) sockets |
Switched outlet group | 2 outlet groups | ||
Communication | |||
1 USB port + 1 serial RS232 port + 1 mini-terminal block for remote ON/OFF + 1 mini-terminal block for remote power off + 1 mini-terminal block for output relay |
|||
Communication slot -1 slot for Gigabit Network management card, Industrial Gateway Card (Modbus TCP/RTU), or Relay card. | |||
Operating conditions, standards and approvals | |||
Operating temeprature | 0 to 40°C | ||
Typical noise level | 35dB | 40dB | |
Safety | IEC/EN 62040-1, UL 1778, CSA 22.2 | ||
EMC | IEC/EN 62040 -2, FCC Class B, CISPR22 Class B | ||
Approvals & markings | CE/CB report (TUV)/ EAC/Energy Star/RCM | ||
Dimensions H x W x D in mm/ weight | |||
1.5kVA | 2.0kVA | 3kVA | |
UPS | 86.5x440x450/15.8Kg | 86.5x440x605/22.1Kg | 86.5x440x605/22.8Kg |
EBM | 42.9x438x448/12Kg | 42.9x438x603/17.4Kg | 42.9x438x603/17.4Kg |
Batteries | ||||||||||||||||||||||
Typical backup times* | 300W | 500W | 800W | 1200W | 1800W | 2400W | ||||||||||||||||
9PX 1500 | 45 | 30 | 20 | 13 | ||||||||||||||||||
9PX 1500 + 1 EBM/4EBM | 114/321 | 76/210 | 52/145 | 33/92 | ||||||||||||||||||
9PX 2000 | 66 | 45 | 30 | 21 | 14 | |||||||||||||||||
9PX 2000 + 1 EBM/4EBM | 170/475 | 112/305 | 78/205 | 52/148 | 35/98 | |||||||||||||||||
9PX 3000 | 68 | 46 | 30 | 21 | 14 | 10.5 | ||||||||||||||||
9PX 3000 + 1 EBM/4EBM | 184/516 | 120/320 | 80/215 | 54/153 | 37/104 | 28/78 | ||||||||||||||||
Lithium-ion battery (LFP) with 8 to 10 years service life, automatic recognition of external battery modules (EBM) |