INPUT

Voltage Range Low Line Transfer 176V AC @ 100% load
110V AC @ 50% load
Low Line Comeback  186V AC @ 100% load
120V AC @ 50% load
High Line Transfer 300V AC
High Line Comeback  290V AC
Frequency Range  46~54Hz@50Hz / 56~64Hz@60Hz 
Phase Single-phase with ground
Power Factor 0.99 @ 100% load

OUTPUT

AC Voltage Regulation
(Batt. Mode)
±1%
Frequency Range
(Synchronized Range) 
46~54Hz @50Hz/56~64Hz @60Hz
Frequency Range
(Batt. Mode)
50Hz ± 0.1Hz or 60Hz ± 0.1Hz
Load Crest Factor 3:1
Harmonic Distortion 2% THD (Linear Load)
6% THD (Linear Load)
Transfer AC Mode to Batt. Mode  Zero
Inverter to Bypass Zero
Waveform (Batt. Mode)  Pure Sinewave

EFFICIENCY

ECO Mode 90%
Battery Mode 88%

PROTECTION

Full Protection Overload, discharge, thermal, short circuit and overcharge protection

COMMUNICATIONS & MANAGEMENT

Interface USB OR RS232 as standard, Intelligent slot for PSSNMP or PSA400 dry contact
Software Power Shield NetGuard Software - supports Windows-based operating Systems, Linux, Unix & Mac
LCD Display / Alarm UPS Status, Load Level, Battery Level, Input/Output Voltage, Battery Time Remaining and Fault Indicators
Audible Alarm Battery Mode, Low Battery, Overload, Fault

PHYSICAL

Dimension (D x W x H) 575 x 250 x 576.5mm
Net Weight 83kg

OPERATING ENVIRONMENT

Temperature 0°C~40°C
Humidity 20%~90% (RH Non-Condensing)
Noise Level Less than 58dB @ 1 Meter

COMPLIANCE

Safety EN62040-1-1 2003, IEC60950-1-1
EMS EN62040-2 2006
RoHS Directive 2001 / 65 / EU