| Rating (VA/W) | 1500VA/1500W | |||||||||||
| Format | RT2U (tower/rack 2U) | |||||||||||
| Electrical Characteristics | ||||||||||||
| Technology | Line-Interactive High Frequency (Pure Sinewave, Booster + Fader) | |||||||||||
| Input voltage range without batteries | 160V-294V (adjustable to 150V-294V) | |||||||||||
| Input frequency range without batteries | 47 to 70 Hz (50Hz system), 56.5 to 70Hz (60Hz system), 40Hz in low-sensitivity mode | |||||||||||
| Output voltage | 230V (+6/-10%)(Adjustable to 200V*/208V/220V/230V/240V), 50/60 Hz +/-0.1 Hz (autosensing) | |||||||||||
| Connections | ||||||||||||
| Input | IEC C14 (10A) | |||||||||||
| Output | (8) IEC C13 (10A) | |||||||||||
| Remote controlled sockets | 2 groups of (2) IEC C13 (10A) | |||||||||||
| Batteries | ||||||||||||
| Typical Backup Times** | 300W | |||||||||||
| 5PX 1500 | 44 | |||||||||||
| Battery management | ABM® Temperature compensated charging method (user selectable). Automatic battery test, deep discharge protection, automatic recognition of external battery units | |||||||||||
| Interfaces | ||||||||||||
| Communication ports | 1 USB port + 1 serial RS232 port + 1 mini-terminal block for Remote ON/OFF + 1 mini-terminal block for Remote Power OFF + 1 mini-terminal block for output relay | |||||||||||
| Communication slot | 1 slot for Network-M2, INDGW-M2, or RELAY-MS cards | |||||||||||
| Operating conditions, standards and approvals | ||||||||||||
| Operating temperature | 0 to 40°C | |||||||||||
| Noise level | ||||||||||||
| Safety | IEC/EN 62040-1, UL1778, CSA22.2 | |||||||||||
| EMC, Performance | IEC/EN 62040-2, FCC Class B, CISPR22 Class B | |||||||||||
| Approvals | CE / CB report (TUV) / cTUVus / EAC / UKCA / Ukr / Cm / RCM | |||||||||||
| Dimensions W x D x H / Weight | ||||||||||||
| UPS Dimensions (mm) | 438x448x85.5 | |||||||||||
| UPS Weight (kg) | 22.4 | |||||||||||
| EBM dimensions (mm) | 438x448x85.5 | |||||||||||
| EBM weight (kg) | 27.8 | |||||||||||
| Customer Service & Support | ||||||||||||
| Warranty | 3 years (See ANZ Warranty Statement) | |||||||||||
| *5% derating @ 200V | ||||||||||||
| **Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. | ||||||||||||