Rating (VA/W) 2200VA/2200W
Format RT2U (tower/rack 2U) 
Electrical characteristics 
Technology On-line double conversion with Power Factor Correction (PFC) system
Nominal voltage 200/208/220/230/240V
Input voltage range 176V~276V without derating (up to 100V~276V with derating)
Input frequency range 40~70Hz, 50/60Hz auto selection, frequency converter mode
Efficiency up to 93.5% in online mode (up to 98% in Hi-efficiency mode)
Connections 
Input 1x IEC C20 (16A) or terminal block on HotSwap MBP HW (Hard-Wired)
Outputs 8x IEC C13 (10A) sockets + 2x IEC C19 (16A) sockets
Outputs on HotSwap models 4x FR/Schuko sockets or 3x BS sockets or 6x IEC 10A sockets or terminal blocks (HW version)
Switched outlet group 2 outlet groups
Batteries 
Typical backup times* 800W
Battery management ABM® & temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units
Communication 
Communication ports 1x USB port + 1x serial RS232 port + 1x mini-terminal block for remote ON/OFF + 1x mini-terminal block for remote power off + 1x mini-terminal block for output relay
Communication slot 1x slot for Network-MS card (included in netpack versions), ModBus-MS or Relay-MS cards
Operating conditions, standards and approvals 
Operating temeprature 0°C~40°C
Typical noise level 40dB
Safety IEC/EN 62040-1, UL 1778, CSA 22.2
EMC IEC/EN 62040 -2, FCC Class B, CISPR22 Class B
Approvals & markings CE /CB report (TUV) / cULus / EAC /RCM / KC / Energy Star
Dimensions H x W x D in mm/ Weight 
UPS 86.5x440x605/25kg
EBM 2U version: 86.5x440x605/39.2kg
Customer service and support 
Warranty 3 years on electronics, 2 years on batteries

* Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.